Event |
Name of Process/Activity
|
Description of
Process/Activity |
Information Producer
|
Information
Receiver |
Name of Info Exchanged
|
IntelliGrid Architecture Environments |
3.2.1-1 |
ADA VVC Controller during event run
|
DOMA
detects load voltage or overload
violation |
DOMA
function detects load voltage or
overload violation and initiates
ADA VVC Controller. |
DOMA
function |
ADA VVC Controller |
Command
to initiate VVC |
Intra-Control Center Environment |
3.2.1-11,
3.2.1-111,
3.2.1-1111
|
|
Checking
real-time data |
DOMA
function checks the real-time data for
changes, alarms. |
DMS
SCADA database |
DOMA
function |
DMS
real-time analog, status, TLQ data,
confirmation of execution of VVC
commands, status of voltage controllers |
Intra-Control Center Environment |
3.2.1-12,
3.2.1-112,
3.2.1-1112 |
|
Checking
real-time data |
DOMA
function checks the real-time data for
changes, alarms. |
SCADA
Energy Management System database |
DOMA
function |
Energy Management System real-time analog,
status, TLQ data |
Intra-Control Center Environment |
3.2.1.13 |
|
Changing
current objective to load reduction
within normal limits due to high energy
price |
DOMA
function detects high-energy price and
issues command to change VVC objective. |
DOMA
function |
ADA VVC Controller |
Command
to change optimization objective |
Intra-Control Center Environment |
3.2.1.14 |
|
VVC
performs optimization according to
current objective |
DOMA
function issues command to initiate VVC. |
DOMA
function |
ADA VVC Controller |
Command
to initiate VVC |
Intra-Control Center Environment |
3.2.2 |
|
VVC
performs optimization according to
current objective |
ADA VVC Controller receives excerpt from
ADA database updated with latest SCADA
scan. |
ADADatabase |
ADA VVC Controller |
ADA
database excerpt |
Intra-Control Center Environment |
3.2.3 |
|
VVC
performs optimization according to
current objective |
VVC
issues information relevant for
System Operator. |
ADA VVC Controller |
System Operator |
VVC
status, present and recommended bus kV,
benefits, expected lowest and highest
load voltages |
User
Interface |
3.2.4 |
|
VVC
performs optimization according to
current objective |
DMS
SCADA database receives results of
optimization. |
ADA VVC Controller |
DMS
SCADA database |
Recommended settings to relevant voltage
and power electronic controllers, DER
modes of operation and settings,
capacitor status |
Intra-Control Center Environment |
3.2.5 |
|
VVC
performs optimization according to
current objective |
Selected
results are archived in
ADA Historic Database. |
ADA VVC Controller |
ADA Historic Database |
VVC and
LTC states and settings; VVC limits and
benefits; losses, voltage, objective
function and total demand before and
after optimization, logs |
Intra-Control Center Environment |
3.2.6 |
|
VVC
performs optimization according to
current objective |
ADA VVC Controller initiates DOMA function
after confirmation of execution is
received. |
ADA VVC Controller |
DOMA
function |
Command
to initiate DOMA |
Intra-Control Center Environment |
3.2.7 |
|
DOMA
function performs analysis |
DOMA
function, after detecting a violation
present during the after-optimization
conditions, sends alarm to
System Operator. |
DOMA
function |
System Operator |
Alarm for System Operator |
User
Interface |
3.2.8 |
|
Prearming RAS function adjusts settings
of relevant groups of load shedding |
DOMA
function, after detecting that
optimization has not eliminated
transmission violation, sends an alarm
to the System Operator and triggers
pre-arming of RAS. |
DOMA
function |
Remedial Action Scheme, System
Operator
|
Information for prearming Remedial
Action Scheme |
User
Interface |
3.2.9 |
|
Data for System Operator |
Relevant
for System Operator VVC and LTC settings,
limits and statuses are displayed. |
DMS
SCADA database |
System Operator |
VVC:
status, integrity, settings, limits,
bandcenter, objective LTC: status,
position |
User
Interface |
3.3.1 |
|
VVC
determines violation can not be
eliminated through optimization |
DOMA
function detects load voltage or voltage
violation. |
DOMA
function |
ADA VVC Controller |
Command
to initiate VVC |
Intra-Control Center Environment |
3.3.2 |
|
VVC
determines violation can not be
eliminated through optimization |
VVC
receives excerpts from ADA database
updated with latest SCADA scan. |
ADA Database |
ADA VVC Controller |
Excerpts
from ADA database |
Intra-Control Center Environment |
3.3.3 |
|
VVC
determines violation can not be
eliminated through optimization |
VVC
initiates MFR to eliminate the
violation. |
ADA VVC Controller |
MFR
function |
Command
to initiate MFR |
Intra-Control Center Environment |
3.3.4 |
|
VVC
determines violation can not be
eliminated through optimization |
ADA
historic database receives logs issued
by VVC. |
ADA VVC Controller |
ADA Historic Database |
Logs |
Intra-Control Center Environment |
3.4.1 |
|
DOMA
function detects distribution model
inconsistency |
After
detecting distribution model
inconsistency, DOMA function sets an
inconsistency flag to put VVC in a
default mode. |
DOMA
function |
ADA VVC Controller |
Distribution model inconsistency flag |
Intra-Control Center Environment |
3.4.2 |
|
VVC
switches to default settings for
portions of distribution system with
inconsistent model |
The fact
that the VVC is switched to default
setting has been issued is received by
DMS SCADA database. |
ADA VVC Controller |
DMS
SCADA database |
Fact
that VVC is switched to default setting |
Intra-Control Center Environment |
3.4.3 |
|
VVC
switches to default settings for
portions of distribution system with
inconsistent model |
Log is
stored in ADA historic database. |
ADA VVC Controller |
ADA Historic Database |
Log |
Intra-Control Center Environment |
3.5.1 |
|
Checking
real-time data |
DOMA
function checks the real-time data for
changes, alarms. |
DMS
SCADA database |
DOMA
function |
DMS
real-time analog, status, TLQ data,
confirmation of execution of VVC
commands, status of voltage controllers |
Intra-Control Center Environment |
3.5.2 |
|
Checking
real-time data |
DOMA
function checks the real-time data for
changes, alarms. |
SCADA
Energy Management System database |
DOMA
function |
Energy Management System real-time analog,
status, TLQ data |
Intra-Control Center Environment |
3.5.3 |
|
VVC
determines there is room for
optimization and performs optimization
within emergency limits |
DOMA
detects transmission emergency limit
violation and issues a command to
initiate VVC. |
DOMA
function |
ADA VVC Controller |
Command
to initiate VVC |
Intra-Control Center Environment |
3.5.4 |
|
VVC
determines there is room for
optimization and performs optimization
within emergency limits |
VVC
receives excerpts from ADA database
updated with latest SCADA scan. |
ADA Database |
ADA VVC Controller |
Excerpts
from ADA database |
Intra-Control Center Environment |
3.5.5 |
|
VVC
determines there is room for
optimization and performs optimization
within emergency limits |
Selected
optimization results are displayed for
the System Operator. |
ADA VVC Controller |
System Operator |
VVC
status, present and recommended bus kV,
expected lowest and highest load V, flag
of using emergency limits |
User
Interface |
3.5.6 |
|
VVC
determines there is room for
optimization and performs optimization
within emergency limits |
DMS
SCADA database receives relevant
optimization results. |
ADA VVC Controller |
DMS
SCADA database |
Recommended settings to relevant voltage
and power electronic controllers, DER
modes of operation and settings,
capacitors status |
Intra-Control Center Environment |
3.5.7 |
|
VVC
determines there is room for
optimization and performs optimization
within emergency limits |
Selected
results are archived in ADA historic
database. |
ADA VVC Controller |
ADA Historic Database |
VVC and
LTC states and settings; VVC limits and
benefits; losses, voltage, objective
function and total demand before and
after optimization, logs |
Intra-Control Center Environment |
3.5.8 |
|
VVC
determines there is room for
optimization and performs optimization
within emergency limits |
ADA VVC Controller initiates DOMA function
after confirmation of execution is
received. |
ADA VVC Controller |
DOMA
function |
Command
to initiate DOMA |
Intra-Control Center Environment |
3.5.9 |
|
DOMA
function performs analysis |
DOMA
function, after detecting a violation
present during the after-optimization
conditions, sends alarm to
System Operator. |
DOMA
function |
System Operator |
Alarm
for System Operator |
User
Interface |
3.5.10 |
|
Prearming RAS adjusts settings of
relevant groups of load shedding |
DOMA
function, after detecting that
optimization has not eliminated
transmission violation, sends an alarm
to pre-arming RAS function. |
DOMA
function |
Prearming of RAS schemes function |
Alarm
for prearming RAS function |
Intra-Control Center Environment |
3.5.11 |
|
Data for
System Operator |
Relevant
for System Operator VVC and LTC settings,
limits, and statuses are displayed. |
DMS
SCADA database |
System Operator |
VVC:
status, integrity, settings, limits,
bandcenter, objective LTC: status,
position |
User