Distribution Operations - Voltage and Var Control (VVC) Function

Contents

Narrative

This application calculates the optimal settings of voltage controller of LTCs, voltage regulators, DERs, power electronic devices, and capacitor statuses optimizing the operations by either following different objectives at different times, or considering conflicting objectives together in a weighted manner. 

It supports three modes of operation:

1.      Closed-loop mode, in which the application runs either periodically (e.g., every 15 min) or is triggered by an event (i.e., topology or objective change), based on real-time information. The application’s recommendations are executed automatically via SCADA control commands.

2.      Study mode, in which the application performs “what-if” studies, and provides recommended actions to the operator.

3.      Look-ahead mode, in which conditions expected in the near future can be studied (from 1 hour through 1 week) by the operator.

The following objectives, which could be preset for different times of the day and overwritten by operator if need to, are supported by the application:

a.       Minimize kWh consumption at voltages beyond given  voltage quality limits (i.e., ensure standard voltages at customer terminals)

b.      Minimize feeder segment(s) overload

c.       Reduce load while respecting given voltage tolerance (normal and emergency)

d.      Conserve energy via voltage reduction

e.       Reduce or eliminate overload in transmission lines

f.        Reduce or eliminate voltage violations on transmission lines

g.       Provide reactive power support for transmission/distribution bus

h.       Provide spinning reserve support

i.         Minimize cost of energy

j.        Provide compatible combinations of above objectives

If, during optimization or execution of the solution, the circuit status changes, the application is interrupted and solution is re-optimized. If, during execution, some operations are unsuccessful, solution is re-optimized without involving the malfunctioning devices. If some of the controllable devices are unavailable for remote control, solution does not involve these devices but takes into account their reaction to changes in operating conditions.

Steps

VVC Function During Scheduled Run 

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

3.1.1

Time for ADA VVC Controller scheduled run 

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology. It also receives the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data, status of voltage controllers, DER modes of operation, and settings

Intra-Control Center Environment

3.1.2

 

Checking real-time data

DOMA function receives the scan of Energy Management System SCADA data to be checked for relevant changes or events.

Energy Management System SCADA database

DOMA function

Energy Management System real-time analog, status, TLQ data

Intra-Control Center Environment

3.1.3

 

VVC performs optimization according to current objective

The fact that no events and changes in connectivity are detected is communicated to ADA VVC Controller. ADA VVC Controller is triggered by the time schedule.

DOMA function

ADA VVC Controller

No events or changes in connectivity detected, command to start scheduled run

Intra-Control Center Environment

3.1.4

 

VVC performs optimization according to current objective

VVC receives the excerpts from ADA database.

ADADatabase

ADA VVC Controller

Excerpts from ADA database

Intra-Control Center Environment

3.1.5

 

VVC performs optimization according to current objective

Relevant results of VVC optimization are displayed for the System Operator.

ADA VVC Controller

System Operator

VVC status, present and recommended bus kV, benefits, expected lowest and highest load voltage

User Interface

3.1.6

 

VVC performs optimization according to current objective

Relevant results of VVC optimization are sent to controllers in the field.

ADA VVC Controller

DMS SCADA database

Recommended settings to relevant voltage and power electronic controllers, DER modes of operation and settings, capacitor status

Intra-Control Center Environment

3.1.7

 

VVC performs optimization according to current objective

Relevant results of VVC optimization are stored in ADA historic database.

ADA VVC Controller

ADA Historic Database

VVC and LTC states and settings; VVC limits and benefits; losses, voltage, objective function and total demand before and after optimization, logs

Intra-Control Center Environment

3.1.8

 

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology and confirmation of execution of VVC commands. It also provides the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data, status of voltage controllers, confirmation of execution of VVC commands

Intra-Control Center Environment

3.1.9

 

Information for System Operator

System Operator’s display is regularly updated with data associated with LTC and VVC performance.

DMS SCADA database

ADA VVC Controller

VVC: status, integrity, settings, limits, bandcenter, objective;

LTC: status, position; bus voltage limits

Intra-Control Center Environment

 

 

VVC Function During Event Run 

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

3.2.1-1

ADA VVC Controller during event run 

DOMA detects load voltage or overload violation

DOMA function detects load voltage or overload violation and initiates ADA VVC Controller.

DOMA function

ADA VVC Controller

Command to initiate VVC

Intra-Control Center Environment

3.2.1-11,

3.2.1-111,

3.2.1-1111

 

 

Checking real-time data

DOMA function checks the real-time data for changes, alarms.

DMS SCADA database

DOMA function

DMS real-time analog, status, TLQ data, confirmation of execution of VVC commands, status of voltage controllers

Intra-Control Center Environment

3.2.1-12,

3.2.1-112,

3.2.1-1112

 

Checking real-time data

DOMA function checks the real-time data for changes, alarms.

SCADA Energy Management System database

DOMA function

Energy Management System real-time analog, status, TLQ data

Intra-Control Center Environment

3.2.1.13

 

Changing current objective to load reduction within normal limits due to high energy price

DOMA function detects high-energy price and issues command to change VVC objective.

DOMA function

ADA VVC Controller

Command to change optimization objective

Intra-Control Center Environment

3.2.1.14

 

VVC performs optimization according to current objective

DOMA function issues command to initiate VVC.

DOMA function

ADA VVC Controller

Command to initiate VVC

Intra-Control Center Environment

3.2.2

 

VVC performs optimization according to current objective

ADA VVC Controller receives excerpt from ADA database updated with latest SCADA scan.

ADADatabase

ADA VVC Controller

ADA database excerpt

Intra-Control Center Environment

3.2.3

 

VVC performs optimization according to current objective

VVC issues information relevant for System Operator.

ADA VVC Controller

System Operator

VVC status, present and recommended bus kV, benefits, expected lowest and highest load voltages

User Interface

3.2.4

 

VVC performs optimization according to current objective

DMS SCADA database receives results of optimization.

ADA VVC Controller

DMS SCADA database

Recommended settings to relevant voltage and power electronic controllers, DER modes of operation and settings, capacitor status

Intra-Control Center Environment

3.2.5

 

VVC performs optimization according to current objective

Selected results are archived in ADA Historic Database.

ADA VVC Controller

ADA Historic Database

VVC and LTC states and settings; VVC limits and benefits; losses, voltage, objective function and total demand before and after optimization, logs

Intra-Control Center Environment

3.2.6

 

VVC performs optimization according to current objective

ADA VVC Controller initiates DOMA function after confirmation of execution is received.

ADA VVC Controller

DOMA function

Command to initiate DOMA

Intra-Control Center Environment

3.2.7

 

DOMA function performs analysis

DOMA function, after detecting a violation present during the after-optimization conditions, sends alarm to System Operator.

DOMA function

System Operator

Alarm for System Operator

User Interface

3.2.8

 

Prearming RAS function adjusts  settings of relevant groups of load shedding

DOMA function, after detecting that optimization has not eliminated transmission violation, sends an alarm to the System Operator and triggers pre-arming of RAS.

DOMA function

Remedial Action Scheme, System Operator

Information for prearming Remedial Action Scheme

User Interface

3.2.9

 

Data for System Operator

Relevant for System Operator VVC and LTC settings, limits and statuses are displayed.

DMS SCADA database

System Operator

VVC: status, integrity, settings, limits, bandcenter, objective LTC: status, position

User Interface

3.3.1

 

VVC determines violation can not be eliminated through optimization

DOMA function detects load voltage or voltage violation.

DOMA function

ADA VVC Controller

Command to initiate VVC

Intra-Control Center Environment

3.3.2

 

VVC determines violation can not be eliminated through optimization

VVC receives excerpts from ADA database updated with latest SCADA scan.

ADA Database

ADA VVC Controller

Excerpts from ADA database

Intra-Control Center Environment

3.3.3

 

VVC determines violation can not be eliminated through optimization

VVC initiates MFR to eliminate the violation.

ADA VVC Controller

MFR function

Command to initiate MFR

Intra-Control Center Environment

3.3.4

 

VVC determines violation can not be eliminated through optimization

ADA historic database receives logs issued by VVC. 

ADA VVC Controller

ADA Historic Database

Logs

Intra-Control Center Environment

3.4.1

 

DOMA function detects distribution model inconsistency

After detecting distribution model inconsistency, DOMA function sets an inconsistency flag to put VVC in a default mode.

DOMA function

ADA VVC Controller

Distribution model inconsistency flag

Intra-Control Center Environment

3.4.2

 

VVC switches to default settings for portions of distribution system with inconsistent model

The fact that the VVC is switched to default setting has been issued is received by DMS SCADA database.

ADA VVC Controller

DMS SCADA database

Fact that VVC is switched to default setting

Intra-Control Center Environment

3.4.3

 

VVC switches to default settings for portions of distribution system with inconsistent model

Log is stored in ADA historic database.

ADA VVC Controller

ADA Historic Database

Log

Intra-Control Center Environment

3.5.1

 

Checking real-time data

DOMA function checks the real-time data for changes, alarms.

DMS SCADA database

DOMA function

DMS real-time analog, status, TLQ data, confirmation of execution of VVC commands, status of voltage controllers

Intra-Control Center Environment

3.5.2

 

Checking real-time data

DOMA function checks the real-time data for changes, alarms.

SCADA Energy Management System database

DOMA function

Energy Management System real-time analog, status, TLQ data

Intra-Control Center Environment

3.5.3

 

VVC determines there is room for optimization and performs optimization within emergency limits

DOMA detects transmission emergency limit violation and issues a command to initiate VVC.

DOMA function

ADA VVC Controller

Command to initiate VVC

Intra-Control Center Environment

3.5.4

 

VVC determines there is room for optimization and performs optimization within emergency limits

VVC receives excerpts from ADA database updated with latest SCADA scan.

ADA Database

ADA VVC Controller

Excerpts from ADA database

Intra-Control Center Environment

3.5.5

 

VVC determines there is room for optimization and performs optimization within emergency limits

Selected optimization results are displayed for the System Operator.

ADA VVC Controller

System Operator

VVC status, present and recommended bus kV, expected lowest and highest load V, flag of using emergency limits

User Interface

3.5.6

 

VVC determines there is room for optimization and performs optimization within emergency limits

DMS SCADA database receives relevant optimization results.  

ADA VVC Controller

DMS SCADA database

Recommended settings to relevant voltage and power electronic controllers, DER modes of operation and settings, capacitors status

Intra-Control Center Environment

3.5.7

 

VVC determines there is room for optimization and performs optimization within emergency limits

Selected results are archived in ADA historic database.

ADA VVC Controller

ADA Historic Database

VVC and LTC states and settings; VVC limits and benefits; losses, voltage, objective function and total demand before and after optimization, logs

Intra-Control Center Environment

3.5.8

 

VVC determines there is room for optimization and performs optimization within emergency limits

ADA VVC Controller initiates DOMA function after confirmation of execution is received.

ADA VVC Controller

DOMA function

Command to initiate DOMA

Intra-Control Center Environment

3.5.9

 

DOMA function performs analysis

DOMA function, after detecting a violation present during the after-optimization conditions, sends alarm to System Operator.

DOMA function

System Operator

Alarm for System Operator

User Interface

3.5.10

 

Prearming RAS adjusts settings of relevant groups of load shedding

DOMA function, after detecting that optimization has not eliminated transmission violation, sends an alarm to pre-arming RAS function.

DOMA function

Prearming of RAS schemes function

Alarm for prearming RAS function

Intra-Control Center Environment

3.5.11

 

Data for System Operator

Relevant for System Operator VVC and LTC settings, limits, and statuses are displayed.

DMS SCADA database

System Operator

VVC: status, integrity, settings, limits, bandcenter, objective LTC: status, position

User Interface

 

 

VVC Function Participation in Severe Emergency in Bulk Power System with Intentional Islands 

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

3.6.1

The bulk power system is separated in near-balanced islands to prevent wide-area blackout. The load shedding schemes operated

Creating transmission islands, and load-shedding by fast acting schemes

The conditions of capacity deficit are detected by Energy Management System/SCADA and submitted to VVC as a trigger for changing the objective and perform in emergency mode.

Transmission Energy Management System, Remedial Action Scheme.

ADA load management functions

Command to initiate VVC in load reduction mode; commands from VVC to IEDs and DERs. 

Intra-Control Center Environment

3.6.2

 

Contingency in bulk power system creates transmission islands

SCADA Energy Management System receives status of switches (circuit breakers) in transmission affected by contingency.

Transmission Energy Management System, Remedial Action Scheme.

SCADA Energy Management System database

Status of switches

Intra-Control Center Environment

3.6.3

 

UFLS balances load and generation and changes distribution circuits connectivity

DMS SCADA database receives status of switches affected by load shedding.

Field Device

DMS SCADA database

Status of switches

Intra-Control Center Environment

3.6.4

 

Update of the topology and load models

DOMA function receives the latest scan of DMS SCADA database and adjusts the distribution operation model for VVC to perform in emergency load reduction mode. .

DMS SCADA database

DOMA function

DMS real-time analog, status, TLO data, status of voltage controllers.

Intra-Control Center Environment

3.6.5

 

Changing VVC current objective to load reduction within emergency limits

DOMA issues a command to change VVC objective and initiate optimization.

DOMA

ADA VVC Controller

Command to change VVC objective and optimization

Intra-Control Center Environment

3.6.6

 

VVC performs optimization with emergency load reduction objective

VVC performs reduction of load not affected by load-shedding schemes to create capacity reserves and restore a portion of shed loads.

ADA VVC Controller

DMS SCADA database

Settings for voltage controllers,

statuses of capacitors, power electronics statuses of DER, modes of operation and settings of DER controllers.

Intra-Control Center Environment

 

 

IntelliGrid Architecture