Event
|
Name of
Process/Activity
|
Description of
Process/Activity
|
Information
Producer |
Information
Receiver |
Name of Info
Exchanged |
IntelliGrid Architecture
Environments |
2.2.1 |
FLIR
second fault (related to first fault
which is not resolved yet) with only
manual switches |
Checking
real-time data |
DOMA
function receives the scan of DMS SCADA
data to be checked for changes in
topology. It also provides the latest
relevant analog data. |
DMS
SCADA database |
DOMA
function |
DMS
real-time analog, status & TLQ data at
time of first fault |
Intra-Control Center Environment |
2.2.2 |
|
Checking
real-time data |
DOMA
function receives the scan of
Energy Management System SCADA data to be
checked for relevant changes or events. |
Energy Management System SCADA database |
DOMA
function |
Energy Management System real-time analog,
status, TLQ data at time of first fault |
Intra-Control Center Environment |
2.2.3 |
|
Checking
real-time data |
DOMA
function receives the scan of
environmental data to be checked for
changes affecting DER performance
forecast. |
Environmental daily data collector |
DOMA
function |
Real-time environmental data for DER
schedule forecast at time of first fault |
Intra-Control Center Environment |
2.2.4 |
|
Checking
real-time data |
DOMA
function receives the scan of latest
schedules of presently active or
authorized for future outages to be
checked for changes. |
Outage Management System |
DOMA
function |
Schedules of presently active or
authorized for future outages at time of
first fault |
Intra-Control Center Environment |
2.2.5 |
|
ADA Topology Update System changes
connectivity |
After
DOMA detects first fault in
distribution, relevant information is
provided to topology function.
|
DOMA
function |
ADA Topology Update System |
First
fault: circuit breaker lockouts, inputs
from Outage Management System |
Intra-Control Center Environment |
2.2.6 |
|
ADA Topology Update System changes
connectivity |
After
first fault is detected, ADA database is
updated. |
ADA Topology Update System |
ADA Database |
Update
of ADA database after first fault
detection |
Intra-Control Center Environment |
2.2.7 |
|
Fault
location sub-function identifies
fault-related protective devices and
de-energized sections |
After
the first fault is detected, topology
function initiates fault location
sub-function of the FLIR function.
|
ADA Topology Update System |
FLIR
function |
Fault
location sub-function initiation after
first fault |
Intra-Control Center Environment |
2.2.8 |
|
Fault
location sub-function identifies
fault-related protective devices and
de-energized sections |
Fault
location sub-function receives the
needed data from ADA database after it
was updated with the first fault
information. |
ADA Database |
FLIR
function |
Excerpts
from ADA database updated after first
fault detection |
Intra-Control Center Environment |
2.2.9 |
|
Fault
location sub-function identifies
fault-related protective devices and
de-energized sections |
Fault
location sub-function provides the
System Operator with information on the
first fault needed for him to make
operational decisions, i.e., dispatching
the field crew, etc. |
FLIR
function |
System Operator |
First
fault: circuit breaker lockouts, inputs
from Outage Management System,
fault-related de-energized sections |
User
Interface |
2.2.10 |
|
System Operator informs field crew |
System Operator authorizes to patrol the
faulted line to locate first fault and
perform binary search if needed. |
System Operator |
Field Personnel |
Authorization to patrol faulted line to
locate first fault |
User
Interface |
2.2.11 |
|
Field Personnel informs System Operator |
After
locating the first fault, the crew
informs the System Operator about the
status of switches involved in initial
fault isolation. |
Field Personnel |
System Operator |
Status
of switches involved in initial first
fault isolation |
User
Interface |
2.2.12,
2.2.13 |
|
Entering
status of switches and faulted section
into ADA database |
The
System Operator enters status of switches
(pseudo-statuses) involved in initial
first fault isolation and the faulted
section into ADA database. |
System Operator |
ADA Database |
ADA
database update after initial isolation
of first fault |
User
Interface |
2.2.14 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
By
entering the faulted section, associated
with first fault, into the ADA database,
the System Operator initiates fault
isolation and service restoration
sub-function. |
System Operator |
FLIR |
Initiation of fault isolation and
service restoration sub-function |
User
Interface |
2.2.15 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
Fault
isolation and service restoration
sub-function receives ADA database
excerpts updated after initial first
fault isolation. |
ADA Database |
FLIR
function |
ADA
database excerpts updated after initial
isolation of first fault |
Intra-Control Center Environment |
2.2.16 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
FLIR
issues a report after the first fault
for archiving in ADA historic database |
FLIR
function |
ADA Historic Database |
Report
including interrupted, un-served and
restored load, and number of customers
after first fault |
Intra-Control Center Environment |
2.2.17 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
A
generated list of recommended switching
orders related to first fault is
presented to the System Operator.
|
FLIR
function |
System Operator |
List of
recommended switching orders related to
first fault |
User
Interface |
2.2.18 |
FLIR
second fault (related to first fault
which is not resolved yet) with only
manual switches |
Checking
real-time data |
DOMA
function receives the scan of DMS SCADA
data to be checked for changes in
topology. It also provides the latest
relevant analog data. |
DMS
SCADA database |
DOMA
function |
DMS
real-time analog, status & TLQ data at
time of second fault |
Intra-Control Center Environment |
2.2.19 |
|
Checking
real-time data |
DOMA
function receives the scan of Energy
Management System SCADA data to be
checked for relevant changes or events. |
Energy Management System SCADA database |
DOMA
function |
Energy Management System real-time analog,
status, TLQ data at time of second fault |
Intra-Control Center Environment |
2.2.20 |
|
Checking
real-time data |
DOMA
function receives the scan of
environmental data to be checked for
changes affecting DER performance
forecast. |
Environmental daily data collector |
DOMA
function |
Real-time environmental data for DER
schedule forecast at time of second
fault |
Intra-Control Center Environment |
2.2.21 |
|
Checking
real-time data |
DOMA
function receives the scan of latest
schedules of presently active or
authorized for future outages to be
checked for changes. |
Outage Management System |
DOMA
function |
Schedules of presently active or
authorized for future outages at time of
second fault |
Intra-Control Center Environment |
2.2.22 |
|
ADA Topology Update System changes
connectivity |
After
DOMA detects second fault in
distribution, relevant information is
provided to topology function.
|
DOMA
function |
ADA Topology Update System |
Second
fault: circuit breaker lockouts, inputs
from Outage Management System |
Intra-Control Center Environment |
2.2.23 |
|
ADA Topology Update System changes
connectivity |
After
second fault is detected, ADA database
is updated. |
ADA Topology Update System |
ADA Database |
Update
of ADA database after second fault
detection |
Intra-Control Center Environment |
2.2.24 |
|
Fault
location sub-function identifies
fault-related protective devices and
de-energized sections |
After
the second fault is detected, topology
function initiates fault location
sub-function of the FLIR function.
|
ADA Topology Update System |
FLIR
function |
Fault
location sub-function initiation after
second fault |
Intra-Control Center Environment |
2.2.25 |
|
Fault
location sub-function identifies
fault-related protective devices and
de-energized sections |
Fault
location sub-function receives the
needed data from ADA database after it
was updated with the second fault
information. |
ADA Database |
FLIR
function |
Excerpts
from ADA database updated after second
fault detection |
Intra-Control Center Environment |
2.2.26
|
|
Fault
isolation and service restoration
sub-function determines whether second
fault impacts switching for first fault |
Fault
isolation and service restoration
sub-function determines whether second
fault impacts switching for first fault.
|
FLIR
function |
FLIR
function |
Second
fault: circuit breaker lockouts, inputs
from Outage Management System,
fault-related de-energized sections |
Intra-Control Center Environment |
2.2.27 |
|
Fault
isolation and service restoration
sub-function determines whether second
fault impacts switching for first fault |
Fault
isolation and service restoration
sub-function cancels the previous
switching order if it needs to. |
FLIR
function |
System Operator |
Cancellation of first-fault-related
switching order |
User
Interface |
2.2.28 |
|
System Operator informs field crew |
System Operator authorizes to patrol the
faulted line to locate second fault and
perform binary search if needed. |
System Operator |
Field Personnel |
Authorization to patrol faulted line to
locate second fault |
User
Interface |
2.2.29 |
|
Field Personnel informs System Operator |
After
locating the second fault, the crew
informs the System Operator about the
status of switches involved in initial
second fault isolation. |
Field Personnel |
System Operator |
Status
of switches involved in initial second
fault isolation |
User
Interface |
2.2.30,
2.2.31 |
|
Entering
status of switches and faulted section
into ADA database |
The
System Operator enters status of switches
(pseudo-statuses) involved in initial
second fault isolation and the faulted
section into ADA database. |
System Operator |
ADA Database |
ADA
database update after initial isolation
of second fault |
User
Interface |
2.2.32 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
By
entering the faulted section, associated
with second fault, into the ADA
database, the System Operator initiates
fault isolation and service restoration
sub-function for both faults.
|
System Operator |
FLIR |
Initiation of fault isolation and
service restoration sub-function |
User
Interface |
2.2.33 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
Fault
isolation and service restoration
sub-function receives ADA database
excerpts updated after initial second
fault isolation. |
ADA Database |
FLIR
function |
ADA
database excerpts updated after initial
isolation of second fault |
Intra-Control Center Environment |
2.2.34 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
FLIR
issues a report after the second fault
for archiving in ADA historic database |
FLIR
function |
ADA Historic Database |
Report
including interrupted, un-served and
restored load, and number of customers
after second fault |
Intra-Control Center Environment |
2.2.35 |
|
Fault
isolation and service restoration
sub-function generates list of
recommended switching orders |
A
generated list of recommended switching
orders related to both faults is
presented to the System Operator.
|
FLIR
function |
System Operator |
List of
recommended switching orders related to
second fault |
User
Interface |
2.2.36 |
|
System Operator informs field crew |
System Operator selects a switching order
and authorizes its implementation. |
System Operator |
Field Personnel |
Switching order authorized for
implementation after second fault
|
User
Interface |
2.2.37 |
|
Field Personnel informs System Operator |
Upon
final isolation and service restoration
to healthy sections, the field crew
informs the System Operator about final
status of relevant switches for the
second fault. |
Field Personnel |
System Operator |
Status
of switches involved in final fault
isolation and service restoration to
healthy sections after second fault. |
User
Interface |
2.2.38,
2.2.39 |
|
Entering
status of switches involved in final
fault isolation and service restoration
to healthy sections into ADA database |
The
System Operator enters status of switches
(pseudo-statuses) involved in final
fault isolation and service restoration
to healthy sections into ADA database |
System Operator |
ADA Database |
ADA
database update after final fault
isolation and service restoration
|
User
Interface |
2.2.40 |
FLIR |
System Operator receives the final
switching order from FLIR and dispatched
the crew to implement it |
FLIR,
System Operator |
System Operator
|
Field Personnel |
Switching order, instructions to the
crew |
User
Interface |
|
|
|
|
|
|
|
|
|