Fault Location, Isolation and Service Restoration (FLIR)

This application detects the fault, determines the faulted section and the probable location of fault, and recommends an optimal isolation of the faulted portions of the distribution feeder and the procedures for the restoration of services to its healthy portions. The key sub-functions performed by the application are as follows:

Fault Location

This sub-function is initiated by SCADA inputs, such as lockouts, fault indications/location, and, also, by inputs from OMS, and, in the future, by inputs from fault-predicting devices.  It determines the specific protective device, which has cleared the sustained fault, identifies the de-energized sections, and estimates the probable place of the actual or the expected fault. It distinguishes faults cleared by controllable protective devices from those cleared by fuses, and identifies momentary outages and inrush/cold load pick-up currents.

Fault Isolation and Service Restoration

This sub-function supports three modes of operation:

1.      Closed-loop mode, in which the sub-function is initiated by the Fault location sub-function. It generates a switching order (i.e., sequence) for the remotely controlled switching devices to isolate the faulted section, and restore service to the non-faulted sections. The switching order is automatically executed via SCADA.  .

2.      Advisory mode, in which the sub-function is initiated by the Fault location sub-function. It generates a switching order for remotely- and manually-controlled switching devices to isolate the faulted section, and restore service to the non-faulted sections. The switching order is presented to operator for approval and execution   

3.      Study mode, in which the sub-function is initiated by the user. It analyzes a saved case modified by the user, and generates a switching order under the operating conditions specified by the user.

If during execution, there is change in connectivity, the sub-function interrupts the execution and re-optimizes the solution based on new conditions. If during service restoration, there is another fault, the sub-function runs again considering a new fault scenario. When work is completed, the sub-function is instructed to generate a switching order for restoration of the normal configuration. The generated switching orders are based on considering the availability of remotely controlled switching devices, feeder paralleling, creation of islands supported by distributed energy resources, and on cold-load pickup currents.

Services

  • ADA indicates faults cleared by controllable protective devices by distinguishing between:

a) faults cleared by fuses

b) momentary outages

c) inrush/cold load current

  • ADA determines the faulted sections based on SCADA fault indications and protection lockout signals
  • ADA estimates the probable fault locations based on SCADA fault current measurements and real-time fault analysis
  • ADA determines the fault-clearing non-monitored protective device based on trouble call inputs and dynamic connectivity model
  • ADA generates switching orders for fault isolation, service restoration, and return to normal (taking into account the availability of remotely controlled switching devices, feeder paralleling, and cold-load pickup):

a) Operator executes switching orders by using SCADA

b) Operator authorizes ADA application to execute switching orders in closed-loop mode

  • ADA isolates the fault and restores service automatically by-passing the operator based on operator’s authorization in advance
  • ADA pre-arms Distributed Intelligence schemes
  • ADA considers creation of islands supported by distributed resources for service restoration
     

Steps

The following FLIR functions are described:

FLIR First Fault with Only Manual Switches

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

2.1.1

FLIR first fault with only manual switches

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data

Intra-Control Center Environment

2.1.2

 

Checking real-time data

DOMA function receives the scan of Energy Management System SCADA data to be checked for relevant changes or events.

Energy Management System SCADA database

DOMA function

Energy Management System real-time analog, status, TLQ data

Intra-Control Center Environment

2.1.3

 

Checking real-time data

DOMA function receives the scan of environmental data to be checked for changes affecting DER performance forecast.

Environmental daily data collector

DOMA function

Real-time environmental data for DER schedule forecast

Intra-Control Center Environment

2.1.4

 

Checking real-time data

DOMA function receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes during the time of repair.

Outage Management System

DOMA function

Schedules of presently active or authorized for future outages

Intra-Control Center Environment

2.1.5

 

ADA Topology Update System changes connectivity

After DOMA detects fault in distribution, relevant information is provided to topology function.

DOMA function

ADA Topology Update System

Circuit breaker lockouts, inputs from Outage Management System

Intra-Control Center Environment

2.1.6

 

ADA Topology Update System changes connectivity

After fault is detected, ADA database is updated.

ADA Topology Update System

ADA Database

Update of ADA database

Intra-Control Center Environment

2.1.7

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Topology function initiates fault location sub-function of the FLIR function.  

ADA Topology Update System

FLIR function

Fault location sub-function initiation

Intra-Control Center Environment

2.1.8

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Fault location sub-function receives the needed data from ADA database after it was updated with fault information.

ADA Database

FLIR function

Excerpts from ADA database updated after fault detection

Intra-Control Center Environment

2.1.9

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Fault location sub-function provides the System Operator with information needed for him to make operational decisions, i.e., dispatching the field crew, etc.

FLIR function

System Operator

Circuit breaker lockouts, inputs from Outage Management System, fault-related de-energized sections

User Interface

2.1.10

 

Fault- location relay informs System Operator

System Operator receives distances to fault location provided by the fault location relay.

Fault location function

System Operator

Distances to fault location

User Interface

2.1.12

 

System Operator informs field crew

System Operator authorizes to patrol the faulted line to locate fault and perform binary search if needed.

System Operator

Field Personnel

Authorization to patrol faulted line

User Interface

2.1.13

 

Field Personnel informs System Operator

After locating the fault, the crew informs the System Operator about the status of switches involved in initial fault isolation.

Field Personnel

System Operator

Status of switches involved in initial fault isolation

User Interface

2.1.14, 2.1.15

 

Entering status of switches and faulted section into ADA database

The System Operator enters status of switches (pseudo-statuses) involved in initial fault isolation and the faulted section into ADA database.

System Operator

ADA Database

ADA database update after initial fault isolation

User Interface

2.1.16

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

By entering the faulted section into the ADA database, the System Operator initiates fault isolation and service restoration sub-function.

System Operator

FLIR

Initiation of fault isolation and service restoration sub-function

User Interface

2.1.17

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated after initial fault isolation.

ADA Database

FLIR function

ADA database excerpts updated after initial fault isolation

Intra-Control Center Environment

2.1.18

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report for archiving in ADA historic database

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers

Intra-Control Center Environment

2.1.19

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A generated list of recommended switching orders is presented to the System Operator.

FLIR function

System Operator

List of recommended switching orders

User Interface

2.1.20

 

System Operator informs field crew

System Operator selects a switching order and authorizes its implementation.

System Operator

Field Personnel

Switching order authorized for implementation

User Interface

2.1.21

 

Field Personnel informs System Operator

Upon final isolation and service restoration to healthy sections, the field crew informs the System Operator about final status of relevant switches (cuts).

Field Personnel

System Operator

Status of switches involved in final fault isolation and service restoration to healthy sections.

User Interface

2.1.22, 2.1.23

 

Entering status of switches involved in final fault isolation and service restoration to healthy sections into ADA database

The System Operator enters status of switches/cuts (pseudo-statuses) involved in final fault isolation and service restoration to healthy sections into ADA database

System Operator

ADA Database

ADA database update after final fault isolation and service restoration

User Interface

2.1.24

 

FLIR updates the switching order in accord with the final fault isolation

System Operator receives the final switching order from FLIR and dispatched the crew to implement it

FLIR,

System Operator

System Operator,

Field Personnel

Switching order, instructions to the crew

User Interface

 

 

FLIR Second Fault (Related to First Fault which is Not Resolved Yet) with Only Manual Switches

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

2.2.1

FLIR second fault (related to first fault which is not resolved yet) with only manual switches

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data at time of first fault

Intra-Control Center Environment

2.2.2

 

Checking real-time data

DOMA function receives the scan of Energy Management System SCADA data to be checked for relevant changes or events.

Energy Management System SCADA database

DOMA function

Energy Management System real-time analog, status, TLQ data at time of first fault

Intra-Control Center Environment

2.2.3

 

Checking real-time data

DOMA function receives the scan of environmental data to be checked for changes affecting DER performance forecast.

Environmental daily data collector

DOMA function

Real-time environmental data for DER schedule forecast at time of first fault

Intra-Control Center Environment

2.2.4

 

Checking real-time data

DOMA function receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes.

Outage Management System

DOMA function

Schedules of presently active or authorized for future outages at time of first fault

Intra-Control Center Environment

2.2.5

 

ADA Topology Update System changes connectivity

After DOMA detects first fault in distribution, relevant information is provided to topology function.

DOMA function

ADA Topology Update System

First fault: circuit breaker lockouts, inputs from Outage Management System

Intra-Control Center Environment

2.2.6

 

ADA Topology Update System changes connectivity

After first fault is detected, ADA database is updated.

ADA Topology Update System

ADA Database

Update of ADA database after first fault detection

Intra-Control Center Environment

2.2.7

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

After the first fault is detected, topology function initiates fault location sub-function of the FLIR function.  

ADA Topology Update System

FLIR function

Fault location sub-function initiation after first fault

Intra-Control Center Environment

2.2.8

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Fault location sub-function receives the needed data from ADA database after it was updated with the first fault information.

ADA Database

FLIR function

Excerpts from ADA database updated after first fault detection

Intra-Control Center Environment

2.2.9

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Fault location sub-function provides the System Operator with information on the first fault needed for him to make operational decisions, i.e., dispatching the field crew, etc.

FLIR function

System Operator

First fault: circuit breaker lockouts, inputs from Outage Management System, fault-related de-energized sections

User Interface

2.2.10

 

System Operator informs field crew

System Operator authorizes to patrol the faulted line to locate first fault and perform binary search if needed.

System Operator

Field Personnel

Authorization to patrol faulted line to locate first fault

User Interface

2.2.11

 

Field Personnel informs System Operator

After locating the first fault, the crew informs the System Operator about the status of switches involved in initial fault isolation.

Field Personnel

System Operator

Status of switches involved in initial first fault isolation

User Interface

2.2.12, 2.2.13

 

Entering status of switches and faulted section into ADA database

The System Operator enters status of switches (pseudo-statuses) involved in initial first fault isolation and the faulted section into ADA database.

System Operator

ADA Database

ADA database update after initial isolation of first fault

User Interface

2.2.14

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

By entering the faulted section, associated with first fault, into the ADA database, the System Operator initiates fault isolation and service restoration sub-function.

System Operator

FLIR

Initiation of fault isolation and service restoration sub-function

User Interface

2.2.15

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated after initial first fault isolation.

ADA Database

FLIR function

ADA database excerpts updated after initial isolation of first fault

Intra-Control Center Environment

2.2.16

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report after the first fault for archiving in ADA historic database

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers after first fault

Intra-Control Center Environment

2.2.17

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A generated list of recommended switching orders related to first fault is presented to the System Operator.

FLIR function

System Operator

List of recommended switching orders related to first fault

User Interface

2.2.18

FLIR second fault (related to first fault which is not resolved yet) with only manual switches

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data at time of second fault

Intra-Control Center Environment

2.2.19

 

Checking real-time data

DOMA function receives the scan of Energy Management System SCADA data to be checked for relevant changes or events.

Energy Management System SCADA database

DOMA function

Energy Management System real-time analog, status, TLQ data at time of second fault

Intra-Control Center Environment

2.2.20

 

Checking real-time data

DOMA function receives the scan of environmental data to be checked for changes affecting DER performance forecast.

Environmental daily data collector

DOMA function

Real-time environmental data for DER schedule forecast at time of second fault

Intra-Control Center Environment

2.2.21

 

Checking real-time data

DOMA function receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes.

Outage Management System

DOMA function

Schedules of presently active or authorized for future outages at time of second fault

Intra-Control Center Environment

2.2.22

 

ADA Topology Update System changes connectivity

After DOMA detects second fault in distribution, relevant information is provided to topology function.

DOMA function

ADA Topology Update System

Second fault: circuit breaker lockouts, inputs from Outage Management System

Intra-Control Center Environment

2.2.23

 

ADA Topology Update System changes connectivity

After second fault is detected, ADA database is updated.

ADA Topology Update System

ADA Database

Update of ADA database after second fault detection

Intra-Control Center Environment

2.2.24

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

After the second fault is detected, topology function initiates fault location sub-function of the FLIR function.  

ADA Topology Update System

FLIR function

Fault location sub-function initiation after second fault

Intra-Control Center Environment

2.2.25

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Fault location sub-function receives the needed data from ADA database after it was updated with the second fault information.

ADA Database

FLIR function

Excerpts from ADA database updated after second fault detection

Intra-Control Center Environment

2.2.26

 

Fault isolation and service restoration sub-function determines whether second fault impacts switching for first fault

Fault isolation and service restoration sub-function determines whether second fault impacts switching for first fault.

FLIR function

FLIR function

Second fault: circuit breaker lockouts, inputs from Outage Management System, fault-related de-energized sections

Intra-Control Center Environment

2.2.27

 

Fault isolation and service restoration sub-function determines whether second fault impacts switching for first fault

Fault isolation and service restoration sub-function cancels the previous switching order if it needs to.

FLIR function

System Operator

Cancellation of first-fault-related switching order

User Interface

2.2.28

 

System Operator informs field crew

System Operator authorizes to patrol the faulted line to locate second fault and perform binary search if needed.

System Operator

Field Personnel

Authorization to patrol faulted line to locate second fault

User Interface

2.2.29

 

Field Personnel informs System Operator

After locating the second fault, the crew informs the System Operator about the status of switches involved in initial second fault isolation.

Field Personnel

System Operator

Status of switches involved in initial second fault isolation

User Interface

2.2.30, 2.2.31

 

Entering status of switches and faulted section into ADA database

The System Operator enters status of switches (pseudo-statuses) involved in initial second fault isolation and the faulted section into ADA database.

System Operator

ADA Database

ADA database update after initial isolation of second fault

User Interface

2.2.32

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

By entering the faulted section, associated with second fault, into the ADA database, the System Operator initiates fault isolation and service restoration sub-function for both faults.

System Operator

FLIR

Initiation of fault isolation and service restoration sub-function

User Interface

2.2.33

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated after initial second fault isolation.

ADA Database

FLIR function

ADA database excerpts updated after initial isolation of second fault

Intra-Control Center Environment

2.2.34

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report after the second fault for archiving in ADA historic database

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers after second fault

Intra-Control Center Environment

2.2.35

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A generated list of recommended switching orders related to both faults is presented to the System Operator.

FLIR function

System Operator

List of recommended switching orders related to second fault

User Interface

2.2.36

 

System Operator informs field crew

System Operator selects a switching order and authorizes its implementation.

System Operator

Field Personnel

Switching order authorized for implementation after second fault

User Interface

2.2.37

 

Field Personnel informs System Operator

Upon final isolation and service restoration to healthy sections, the field crew informs the System Operator about final status of relevant switches for the  second fault.

Field Personnel

System Operator

Status of switches involved in final fault isolation and service restoration to healthy sections after second fault.

User Interface

2.2.38, 2.2.39

 

Entering status of switches involved in final fault isolation and service restoration to healthy sections into ADA database

The System Operator enters status of switches (pseudo-statuses) involved in final fault isolation and service restoration to healthy sections into ADA database

System Operator

ADA Database

ADA database update after final fault isolation and service restoration

User Interface

2.2.40

FLIR

System Operator receives the final switching order from FLIR and dispatched the crew to implement it

FLIR,

System Operator

System Operator

 

Field Personnel

Switching order, instructions to the crew

User Interface

                 

 

  

FLIR Fault with Remotely-Controlled and Manual Switches

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

2.3.1

FLIR fault with remotely-controlled and manual switches

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data

Intra-Control Center Environment

2.3.2

 

Checking real-time data

DOMA function receives the scan of Energy Management System SCADA data to be checked for relevant changes or events.

Energy Management System SCADA database

DOMA function

Energy Management System real-time analog, status, TLQ data

Intra-Control Center Environment

2.3.3

 

Checking real-time data

DOMA function receives the scan of environmental data to be checked for changes affecting DER performance forecast.

Environmental daily data collector

DOMA function

Real-time environmental data for DER schedule forecast

Intra-Control Center Environment

2.3.4

 

Checking real-time data

DOMA function receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes.

Outage Management System

DOMA function

Schedules of presently active or authorized for future outages

Intra-Control Center Environment

2.3.5

 

Checking real-time data

DOMA function receives the distance to fault location, which is provided by Fault location function in the presence of the fault.

Fault location function

DOMA function

Distance to fault location

Intra-Control Center Environment

2.3.6

 

ADA Topology Update System changes connectivity

After DOMA detects fault in distribution, relevant information is provided to topology function.

DOMA function

ADA Topology Update System

Circuit breaker lockouts, inputs from Outage Management System

Intra-Control Center Environment

2.3.7

 

ADA Topology Update System changes connectivity

After fault is detected, ADA database is updated.

ADA Topology Update System

ADA Database

Update of ADA database

Intra-Control Center Environment

2.3.8

 

Fault location sub-function identifies fault-related protective devices and de-energized sections

Topology function initiates fault location sub-function of the FLIR function.  

ADA Topology Update System

FLIR function

Fault location subfunction initiation

Intra-Control Center Environment

2.3.9

 

Fault location subfunction identifies fault-related protective devices and de-energized sections

Fault location subfunction receives the needed data from ADA database after it was updated with fault information.

ADA Database

FLIR function

Excerpts from ADA database updated after fault detection

Intra-Control Center Environment

2.3.10

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault location subfunction initiates fault isolation and service restoration sub-function of the FLIR function.  

Fault location function

Fault isolation and service restoration subfunction

Fault isolation and service restoration sub-function initiation, probable fault location with alternatives

Intra-Control Center Environment

2.3.11

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated with fault information.

ADA Database

FLIR function

ADA database excerpts

Intra-Control Center Environment

2.3.12

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report for archiving in ADA historic database.

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers before additional fault isolation

Intra-Control Center Environment

2.3.13a

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A list of recommended switching orders using remotely controlled switches is presented to the System Operator.

FLIR function

System Operator

List of switching orders recommended after fault detection

User Interface

2.3.13b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

In advisory mode, System Operator considers the list of switching order alternatives and selects the best SO based on predefined criteria

FLIR function

System Operator

List of switching orders recommended after fault detection

User Interface

2.3.14a

 

SO execution

In the advisory mode, the System Operator, after reviewing SO, issues supervisory commands to execute it.

System Operator

DMS SCADA database

Supervisory command to execute SO issued after fault detection

User Interface

2.3.14b

 

SO execution

In the closed-loop mode, FLIR issues command to execute the best SO.

FLIR

DMS SCADA database

Supervisory command to execute SO issued after fault detection

Intra-Control Center Environment

2.3.15

 

System Operator informs field crew

System Operator authorizes to patrol the faulted section to accurately locate the fault and perform binary search if needed.

System Operator

Field Personnel

Authorization to patrol faulted line

User Interface

2.3.16

 

Field Personnel informs System Operator

After accurately locating the fault, the crew informs the System Operator about the status of switches involved in additional switching to isolate the smallest possible faulted section.

Field Personnel

System Operator

Status of switches involved in isolating the smallest possible faulted section

User Interface

2.3.17, 2.3.18

 

Entering status of switches and faulted section into ADA database

The System Operator enters status of switches (pseudo-statuses) involved in finall fault isolation and the faulted section into ADA database.

System Operator

ADA Database

ADA database update additional fault isolation

User Interface

2.3.19

 

Entering status of switches and faulted section into ADA database

Entering the faulted section into ADA database initiates FLIR for generating final SO

ADA Database

FLIR

Fault isolation and service restoration sub-function initiation after additional fault isolation

Intra-Control Center Environment

2.3.20

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated after additional fault isolation.

ADA Database

FLIR function

ADA database excerpts

Intra-Control Center Environment

2.3.21

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report for archiving in ADA historic database.

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers after additional fault isolation

Intra-Control Center Environment

2.3.22a

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A list of recommended final switching orders is presented to the System Operator.

FLIR function

System Operator

List of switching orders recommended after additional fault isolation

User Interface

2.3.23a

 

SO execution

In the advisory mode, the System Operator, after reviewing SO, issues supervisory commands to execute it.

System Operator

DMS SCADA database

Supervisory command to execute SO issued after additional fault isolation

User Interface

2.3.23b

 

SO execution

In the closed-loop mode, FLIR issues commands to execute SO.

FLIR

DMS SCADA database

Supervisory command to execute SO issued after additional fault isolation

Intra-Control Center Environment

 

 

 

FLIR Fault with Remotely-Controlled and Manual Switches and Distributed Intelligence System (DIS)

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

2.4.1a

Fault with remotely-controlled and manual switches and with DIS

DIS identifies relevant protective device, de-energized sections and probable fault location and finds service restoration solution

Distributed Intelligence System (DIS) receives the real-time local status and analog data.

IEDs of DIS members

Distributed Intelligence Schemes

Real-time local status and analog data

Intra-Control Center Environment

2.4.2a

 

DIS identifies relevant protective device, de-energized sections and probable fault location and finds service restoration solution

DIS communicates to DIS members the switching instructions for fault isolation and service restoration.

Distributed Intelligence Schemes

IEDS of DIS members

Command to isolate fault and restore service to healthy sections.

Intra-Control Center Environment

2.4.3a

 

DIS identifies relevant protective device, de-energized sections and probable fault location and finds service restoration solution

Changes in connectivity implemented by DIS are downloaded into DMS SCADA database.

Distributed Intelligence Schemes

DMS SCADA database

Changes in connectivity implemented by DIS

Intra-Control Center Environment

2.4.4a

 

Checking real-time data

DOMA function receives the scan of DMS SCADA data to be checked for changes in topology. It also receives the latest relevant analog data.

DMS SCADA database

DOMA function

DMS real-time analog, status & TLQ data, phasor data from WAMACS

Intra-Control Center Environment

2.4.5a

 

Checking real-time data

ADA Topology Update System receives the changes in connectivity implemented by DIS

DOMA function

ADA Topology Update System

Changes in connectivity implemented by DIS

Intra-Control Center Environment

2.4.6a

 

ADA Topology Update System changes connectivity

ADA database is updated with changes in connectivity implemented by DIS

ADA Topology Update System

ADA Database

Changes in connectivity implemented by DIS

Intra-Control Center Environment

2.4.1b

 

DIS identifies relevant protective device, de-energized sections and probable fault location and can not find service restoration solution

Distributed Intelligence System (DIS) receives real-time local status and analog data.

IEDs of DIS members

Distributed Intelligence Schemes

Real-time status and analog data

Intra-Control Center Environment

2.4.2b

 

DIS identifies relevant protective device, de-energized sections and probable fault location and can not find service restoration solution

Indication of DIS inability to find a solution is downloaded into DMS SCADA database.

Distributed Intelligence Schemes

DMS SCADA database

Indication of DIS inability to find a solution

Intra-Control Center Environment

2.4.3b

 

Checking real-time data

Due to DIS inability to find a solution, ADA is initiated.

DMS SCADA database

DOMA function

Command to initiate ADA, DMS real-time analog, status & TLQ data

Intra-Control Center Environment

2.4.4b

 

Checking real-time data

DOMA function receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes.

Outage Management System

DOMA function

Schedules of presently active or authorized for future outages

Intra-Control Center Environment

2.4.5b

 

Checking real-time data

DOMA function receives the scan of Energy Management System SCADA data to be checked for relevant changes or events.

Energy Management System SCADA database

DOMA function

Energy Management System real-time analog, status, TLQ data

Intra-Control Center Environment

2.4.6b

 

Checking real-time data

DOMA function receives the scan of environmental data to be checked for changes affecting DER schedule forecast.

Environmental daily data collector

DOMA function

Real-time environmental data for DER schedule forecast

Intra-Control Center Environment

2.4.7b

 

Checking real-time data

DOMA function receives the distance to fault location, which is provided by fault-locating relay in the presence of the fault.

Fault location function

DOMA function

Distance to fault location

Intra-Control Center Environment

2.4.8b

 

ADA Topology Update System changes connectivity

After DOMA detects fault in distribution, relevant information is provided to topology function.

DOMA function

ADA Topology Update System

Circuit breaker lockouts, inputs from Outage Management System

Intra-Control Center Environment

2.4.9b

 

ADA Topology Update System changes connectivity

After fault is detected, ADA database is updated.

ADA Topology Update System

ADA Database

Update of ADA database

Intra-Control Center Environment

2.4.10b

 

Fault location subfunction identifies fault-related protective devices and de-energized sections

Topology function initiates fault location sub-function of the FLIR function.  

ADA Topology Update System

FLIR function

Fault location subfunction initiation

Intra-Control Center Environment

2.4.11b

 

Fault location subfunction identifies fault-related protective devices and de-energized sections

Fault location subfunction receives the needed data from ADA database after it was updated with fault information.

ADA Database

FLIR function

Excerpts from ADA database updated after fault detection

Intra-Control Center Environment

2.4.12b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault location subfunction initiates fault isolation and service restoration sub-function of the FLIR function.  

Fault location function

Fault isolation and service restoration subfunction

Fault isolation and service restoration sub-function initiation, probable fault location with alternatives

Intra-Control Center Environment

2.4.13b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated with fault information.

ADA Database

FLIR function

ADA database excerpts

Intra-Control Center Environment

2.4.14b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report for archiving in ADA historic database.

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers before additional fault isolation

Intra-Control Center Environment

2.4.15b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A list of recommended switching orders is presented to the System Operator.

FLIR function

System Operator

List of switching orders recommended after fault detection

User Interface

2.4.16b

 

SO execution

In the advisory mode, the System Operator, after reviewing SO, issues a supervisory command to execute it.

System Operator

DMS SCADA database

Supervisory command to execute SO issued after fault detection

User Interface

2.4.17b

 

System Operator informs field crew

System Operator authorizes to patrol the faulted line to accurately locate fault.

System Operator

Field Personnel

Authorization to patrol faulted line

User Interface

2.4.18b

 

Field Personnel informs System Operator

After locating the fault, the crew informs the System Operator about the status of switches involved in additional switching to isolate the smallest possible faulted section.

Field Personnel

System Operator

Status of switches involved in isolating the smallest possible faulted section

User Interface

2.4.19b, 2.4.20b

 

Entering status of switches and faulted section into ADA database

The System Operator enters status of switches (pseudo-statuses) involved in final fault isolation and the faulted section into ADA database.

System Operator

ADA Database

ADA database update additional fault isolation

User Interface

2.4.21b

 

Entering status of switches and faulted section into ADA database

Entering the faulted section into ADA database initiates FLIR

ADA Database

FLIR

Fault isolation and service restoration sub-function initiation after additional fault isolation

Intra-Control Center Environment

2.4.22b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

Fault isolation and service restoration sub-function receives ADA database excerpts updated after additional fault isolation.

ADA Database

FLIR function

ADA database excerpts

Intra-Control Center Environment

2.4.23b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

FLIR issues a report for archiving in ADA historic database.

FLIR function

ADA Historic Database

Report including interrupted, un-served and restored load, and number of customers after additional fault isolation

Intra-Control Center Environment

2.4.24b

 

Fault isolation and service restoration sub-function generates list of recommended switching orders

A list of recommended switching orders is presented to the System Operator.

FLIR function

System Operator

List of switching orders recommended after additional fault isolation

User Interface

2.4.25b

 

SO execution

The System Operator, after reviewing SO, issues a supervisory command to execute it, if remotely controlled switches are used. If manual switches are involved, the System Operator dispatches the crew to implement the switching order. 

System Operator

DMS SCADA database

Supervisory command to execute SO issued after additional fault isolation; instructions for the crew.

User Interface

 

 

 FLIR Fault with DER Connected to Healthy Section

 

 

#

Event

Name of Process/Activity

Description of
Process/Activity

Information Producer

Information
Receiver

Name of Info Exchanged

IntelliGrid Architecture Environments

2.5.1

Fault in a circuit with DER connected to healthy section cleared by fast circuit breaker trip and by reverse protection from DER fault injection creating a self-sufficient island

Unintentional self-sufficient island is created

DOMA receives the scan of DMS SCADA data and historic load data to be checked for changes in topology and loading during the time of repair.

DMS SCADA database

DOMA

DMS real-time analog, status & TLQ data, phasor data from WAMACS

Intra-Control Center Environment

2.5.2a

 

Checking the sufficiency of the island during the time of repair

DOMA determines the sufficiency of the island during the time of repair and enables FLIR for location of the fault within the de-energized section. 

DOMA

FLIR

Instructions to FLIR

Intra-Control Center Environment

2.5.2b

 

Checking the sufficiency of the island during the time of repair

DOMA determines the insufficiency of the island during the portion of time of repair and enables FLIR for location of the fault within the de-energized section and solving restoration for the customers connected to the island. 

DOMA

FLIR

Instructions to FLIR

Intra-Control Center Environment

2.5.3

Fault in a circuit with DER connected to healthy section cleared by fast circuit breaker trip and by reverse protection from DER fault injection, creating an insufficient island

Unintentional insufficient island is created, DER is separated with or without balanced load

DOMA receives the scan of DMS SCADA data and historic load data to be checked for changes in topology and loading during the time of repair.

DMS SCADA database

DOMA

DMS real-time analog, status & TLQ data, phasor data from WAMACS

Intra-Control Center Environment

2.5.4

 

Checking the sufficiency of the island during the time of repair

DOMA determines the insufficiency of the island during the time of repair and enables FLIR for location of the fault within the de-energized section and solving restoration for the de-energized customers connected to the island. 

DOMA

FLIR

Instructions to FLIR

Intra-Control Center Environment

2.5.5

Fault in a circuit with DER connected to healthy section cleared by circuit breaker and by relay protection of DER at the PCC

The feeder is de-energized, DER is separated with or without balanced load

DOMA receives the scan of DMS SCADA data and historic load data to be checked for changes in topology and loading during the time of repair.

DMS SCADA database

DOMA

DMS real-time analog, status & TLQ data, phasor data from WAMACS

Intra-Control Center Environment

2.5.6

 

Checking the topology to ensure that DER is separated

DOMA determines the after-fault topology, the loading during the time of repair, and enables FLIR for location of the fault and solving isolation of the fault and restoration for the de-energized customers connected to the healthy portions of the feeder. 

DOMA

FLIR

Instructions to FLIR

Intra-Control Center Environment

 